A Critical Evaluation of the NSF Standard 61/Section 9 Test in Relation to Lead Leaching Edwards, Marc; Triantafyllidou, Simoni Edition: Vol. - No.American Water Works Association / 01-Jun-2006 / 10 pages
The ANSI/NSF Standard 61/ Section 9 protocol is critically evaluatedfrom the perspective of the leaching solution chemistry. A detailed examination revealsthat the test water is roughly representative of a typical water supply. However, somelower pH and lower alkalinity waters tend to be much more aggressive than the existingsection 9 water, which may cause utilities problems with first draw compliance for thelead and copper rule, even for products that are section 9 certified. Includes 12 references, figures.
Keywords: Lead; Leaching; Standards; Alkalinity; Utilities; Water Supply; Compliance; Copper; pH